Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
37
Table 15. 380V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Separate
Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
675
675
750
750
825
825
900
900
1000
1000
1100
1100
Input and Output Voltage
Volts
380/380 380/380 380/380 380/380 380/380 380/380
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1200
1363
1500
1600
1818
2000
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(6)
500
(6)
500
(6)
500
(8)
500
(8)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
1026
1139
1253
1367
1519
1671
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
500
(8)
DC Input from Battery Disconnect to Each
UPS UPM
(1) Positive, (1) Negative
C
Amps per UPM
603
603
603
603
603
603
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Total Amps
1026
1139
1253
1367
1519
1671
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
500
(8)
NOTE Callout letters
A
,
B
,
C
, and
D
map to
.
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly,
however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly
(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the
return current path and cause a loss of all phase-to-neutral loads
.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
Terminals E1A through E5A and E9A through E11A are stud type terminals. The intercabinet power wiring
connections for this equipment are rated at 90°C. See
for intercabinet power cable terminations and
for supplied intercabinet wiring terminal hardware.
The torque values listed in
for the M8 studs are the maximum allowable. Tightening further will risk
breaking or twisting the stud.
through
show the location of the intercabinet power cable terminals inside the UPS.