155
C
Chhaapptteerr 1100 P
Prroodduucctt S
Sppeecciiffiiccaattiioonnss
1100..11
M
Mooddeell N
Nuum
mbbeerrss
The UPS is housed in two free-standing cabinets with safety shields behind the door and front panels. The UPS
is available in 50 or 60 Hz with various output power ratings.
Model
Power Rating
Frequency
Eaton 9395C-1000/1000
Eaton 9395C-1000/1100
Eaton 9395C-1100/1100
1000 kW, 1000 kVA
50/60 Hz
1000 kW, 1100 kVA
50/60 Hz
1100 kW, 1100 kVA
50/60 Hz
1100..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, environmental, and battery specifications for the UPS.
1100..22..11 U
UP
PS
S IInnppuutt
Operating Input Voltage
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
Reduced for Generator Adjustable
Input Current Harmonic Content
<3% THD at full load
Power Factor
Minimum 0.99 at full load
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage
480 Vdc
Battery Charging Capacity
Up to 480A with less than 85% load
Up to 80A with 100% load
Battery UVR
48 Vdc