Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
121
Figure 74. Path of Current Through the UPS in Battery Mode
Static
Switch
K5
r
e
tr
e
v
n
I
r
e
if
it
c
e
R
K1
K3
Battery
Converter
Battery
Battery
Breaker
Main Power Flow
Trickle Current
Energized
De-Energized
Closed
Open
Breakers
Contactors
K2
Bypass
Breaker
(CB4)
Bypass Input
Rectifier
Input
Output
Input
Breaker
(CB1
NOTE
On a UPS configured as an IOM, the bypass input, static switch, bypass breaker (CB4), and K5 are not present.
NOTE
On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present.
If the input power fails to return or is not within the acceptance windows required for normal operation, the
battery continues discharging until a DC voltage level is reached where the inverter output can no longer
support the connected loads. When this event occurs, the UPS issues another set of audible and visual alarms
indicating SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output can be supported
for only two minutes before the output of the system shuts down. If the bypass source is available, the UPS
transfers to bypass instead of shutting down.
If at any time during the battery discharge the input power becomes available again, contactors K1 and K5 close
and the rectifier begins to supply DC current to the converter and inverter. At this point, the unit returns to
Online mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms
may be seen for a short time due to the current required to recharge the battery.
66..33
S
Siinnggllee U
UP
PS
S S
Syysstteem
m O
Onneelliinnee C
Coonnffiigguurraattiioonnss
The system oneline drawings in this section show the simplified internal structure of the UPS, battery supply,
and basic maintenance bypass.