Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Figure 49. Terminal Blocks TB1, TB2, and TB3 Connector Assignments
UPS
Building Alarm 3
Building Alarm 3 Return
Building Alarm 4
Building Alarm 5
Building Alarm 4 Return
Building Alarm 5 Return
NOTE
All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either
normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer-supplied.
NOTE
The building alarms can be programmed to display the alarm functional name.
NOTE
A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used.
1
10
1
10
TB1
TB2
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
REPO NO
REPO NC
REPO Return
Battery Aux
Battery Aux Common
Battery Shunt Trip
+
Battery Shunt Trip –
UPS
1
10
TB3
Building Alarm 1 Return
Building Alarm 1
Building Alarm 2 Return
Building Alarm 2
Alarm Relay Common
Pull Chain
Pull Chain Common
REPO Return
Output Contactor K3 NC Aux Common
Output Contactor K3 NC Aux