UPS Installation Plan and Unpacking
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
3-3
Figure 3-1. UPS Cabinet Dimensions (Front View)
Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output Voltage
Heat Rejection
BTU/hr
¢
1000 (kg-cal/hr)
Ventilation Required for Cooling Air
Exhaust
Power Xpert
9395-550/225
225 kVA
400/400
43 (10943)
Approximately 826 liter/sec (1750 cfm)
480/480
44 (11054)
Power Xpert
9395-550/275
275 kVA
400/400
53 (13375)
480/480
54 (13510)
Power Xpert
9395-550/450
450 kVA
400/400
87 ((21886)
Approximately 1652 liter/sec (3500 CFM)
480/480
88 (22107)
Power Xpert
9395-550/500
500 kVA
400/400
96 (24318)
480/480
97 (24563)
Power Xpert
9395-550/550
550 kVA
400/400
106 (26749)
480/480
107 ((27020)
Dimensions are in millimeters [inches].
1873.9
[73.8]
1333.8
[52.5]