Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
10-1
Chapter 10 Product Specifications
10.1
Model Numbers
The UPS is housed in a free–standing cabinet with safety shields behind the door and front panels. The UPS is
available in 50 or 60 Hz with various output power ratings.
10.2
Specifications
The following sections detail the input, output, battery, and environmental specifications for the UPS.
10.2.1 UPS Input
Models
Power Rating
Frequency
Power Xpert 9395-550/225
225 kVA
50/60 Hz
Power Xpert 9395-550/275
275 kVA
50/60 Hz
Power Xpert 9395-550/450
450 kVA
50/60 Hz
Power Xpert 9395-550/500
500 kVA
50/60 Hz
Power Xpert 9395-550/550
550 kVA
50/60 Hz
Operating Input Voltage
400 Vac
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3-4 through Table 3-8.
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801
4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc
Summary of Contents for Power Xpert 9395 550/275
Page 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 2: ......
Page 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Page 27: ...Section 1 Installation...
Page 28: ......
Page 207: ......
Page 208: ...164201716 8 164201716 8...