18
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
Table 4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
Power Xpert
9395-550/225
225 kVA
400/400
43 (10943)
Approximately 826 liter/sec (1750
CFM)
480/480
44 (11054)
Power Xpert
9395-550/275
275 kVA
400/400
53 (13375)
480/480
54 (13510)
Power Xpert
9395-550/450
450 kVA
400/400
87 (21886)
Approximately 1652 liter/sec (3500
CFM)
480/480
88 (22107)
Power Xpert
9395-550/500
500 kVA
400/400
96 (24318)
480/480
97 (24563)
Power Xpert
9395-550/550
550 kVA
400/400
106 (26749)
480/480
107 (27020)
Figure 3. UPS Cabinet Dimensions (Front View)
Dimensions are in millimeters [inches].
1873.9
[73.8]
1333.8
[52.5]