Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
153
8.
On the System Status screen, select the
UPM
command. he UPS Control Command screen is displayed.
9.
On the UPS Control Command screen, select the
UPM 1
command.
10. Press the
CONTROLS
pushbutton on the System Status Command menu bar. The UPM 1 Control
Command screen is displayed.
11. Proceed to Step 14.
12. On the System Status screen, select the
UPM
command.
13. Press the
CONTROLS
pushbutton on the System Status Command menu bar. The UPM 1 Control
Command screen is displayed.
14. On the UPM 1 Control Command screen, select
UPM OFF
.
15. Press the
SELECT
pushbutton on the UPM 1 Command menu bar. The UPM status indicates
SHUTDOWN
.
The input, output, and battery contactors open, and the power module is turned off.
Logic power remains on.
16. If UPM 4 (FI-UPM) is installed, repeat Steps 9 through 15 selecting
UPM 4
to shut down UPM 4.
17. Verify the battery breaker or disconnect for the UPS being shut down is open. If not, open the breaker.
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
NOTE
If the UPS contains an input breaker (CB1), DO NOT open the breaker unless no input
feeder breaker is installed.
18. Open the input and bypass feeder circuit breakers for the UPS being shut down.
The UPS is now completely shut down.
External Communications Failure alarm is active on remaining online UPSs. This is an expected event and
will clear upon UPS restart.
77..44..2244 S
Siinnggllee U
UP
PS
S R
Reessttaarrtt
To restart a single UPS from a shutdown state:
1.
Close the MOB for the UPS being restarted.
2.
Close UPS input and bypass feeder circuit breakers for the UPS being restarted.
3.
Unfasten the front door latch and swing the door open on the UPS being restarted (see
).
4.
If input breaker (CB1) is installed on the UPS being restarted and is open, close the breaker.
5.
Close the door and secure the latch.
6.
On the UPS being restarted, observe the UPS control panel display becoming active, indicating logic
power.
7.
On the UPS being restarted, press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
8.
On the System Status screen, verify the UPS status is
SHUTDOWN
and the UPM status is
SHUTDOWN
.
9.
Close the battery breaker for the UPS being restarted.
10. Verify no alarms are active on UPS being restarted.