4 Commissioning
4.5 Acyclic data
50
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
Table 15: List of parameters
PNU
Index
PNU
Subindex
Parameter number in
specific device
Access right
Data type
Name
Description
DA1
DC1
DE1
RUN/
STOP
ro/rw
1
7601
✓
P00-03
P00-03
STOP
ro
N2
Frequency reference
value
4000
hex
= 100 %
100 % = 20.1
7601
✓
–
–
STOP
ro
N2
Speed reference value
4000
hex
= 100 %
100 % = 20.1
3
P0-06
–
–
STOP
ro
N2
MotorPotentiometer
setpoint
4000
hex
= 100 %
100 % = 20.1
2
1
P0-05
–
–
STOP
ro
N2
Torque Reference
Torque control reference
5
1
P2-01
P-20
P-20
RUN
rw
N2
f-Fix1
Fixed frequency 1
4000
hex
= 100 %
100 % = 20.1
2
P2-02
P-21
P-21
RUN
rw
N2
f-Fix2
Fixed frequency 2
4000
hex
= 100 %
100 % = 20.1
3
P2-03
P-22
P-22
RUN
rw
N2
f-Fix3
Fixed frequency 3
4000
hex
= 100 %
100 % = 20.1
4
P2-04
P-23
P-23
RUN
rw
N2
f-Fix4
Fixed frequency 4
4000
hex
= 100 %
100 % = 20.1
5
P2-05
–
–
RUN
rw
N2
f-Fix5
4000
hex
= 100 %
100 % = 20.1
6
P2-06
–
–
RUN
rw
N2
f-Fix6
4000
hex
= 100 %
100 % = 20.1
7
P2-07
–
–
RUN
rw
N2
f-Fix7
4000
hex
= 100 %
100 % = 20.1
8
P2-08
–
–
RUN
rw
N2
f-Fix8
4000
hex
= 100 %
100 % = 20.1
20
0
P1-02
P-02
P-02
STOP
rw
U16
f-min
Used to set the minimum
output frequency; can be set
to any value between 0 and
f-max
3000
≙
50 Hz
1
P1-01
P-01
P-01
STOP
rw
U16
f-max
Used to set the maximum
output frequency; can be set
to any value between f-min
and five times the motor's
rated frequency
3000
≙
50 Hz
2
P0-04
–
–
STOP
rw
f-PreRamp
Speed controller setpoint
3
P0-63
–
–
STOP
rw
f-PostRamp
Speed reference value post
ramp
21
0
P2-09
P-26
–
STOP
rw
U16
f-Skip1
3000
≙
50 Hz
22
0
P2-10
P-27
–
STOP
rw
U16
f-SkipBand1
3000
≙
50 Hz
23
0
P4-10
P-28
–
STOP
rw
U16
f-Umax
Details in Hz
24
0
P4-11
P-29
–
STOP
rw
U16
U-max
Details in Volt