Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
Table 9. BCMS Alarms and Warnings: Normal and Power-KWH Points Lists
BCMS Alarms and Warnings: Normal and Power-KWH Points Lists
BC = branch circuit, PB = panelboard
Branch Circuit Alarms and Warnings
Zero current registers (3 registers, 1 bit for
each branch circuit)
Alarms for active circuits that go to zero current, one bit set for each BC with zero
current reading
Warning registers (3 registers, 1 bit for each
BC)
Summary status, one bit set for each BC in warning
Alarm registers (3 registers, 1 bit for each BC)
Summary status, one bit set for each BC in alarm
Quick status alarm (1 register)
Summary alarm for BCs: one bit set for each alarm/warning/zero current register
that is in an alarm state
Panelboard Alarms
Note: All over/under panelboard alarms are based on thresholds specified in setup.
Over/under current panelboard
Current to PBs is measured from main feed CTs or computed by BCMS from
branch circuits and compared to specified thresholds
Over/under current both panelboards
Current values are summed for both PBs and compared to specified thresholds.
Over/under voltage panelboard
Voltage to PB is outside specified thresholds.
Summary of Contents for PDI JCOMM
Page 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Page 4: ......
Page 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Page 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Page 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Page 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Page 50: ...P 16400110701 P 164001107 01...