4
Eaton PDI JCOMM Enclosure Installation and Operation Manual P-164001107—Rev 01
22..22
JJC
CO
OM
MM
M S
Sppeecciiffiiccaattiioonnss
Table 1. JCOMM Specifications
Product Specifications
Monitoring Capabilities
BCMS Data Acquisition Boards
1 or 2 BCMS boards
Points list (Modbus register map) options
Normal
list (specialized for customized alarms) or
Power-KWH
list (specialized for
power measurements)
IEC
points (specialized for IEC panelboards)
1-2 Voltage sources
208/120VAC/60Hz 3-phase 4-wire
42-168 Branch circuits
Monitored with split-core 60A current transformers (CTs)
2-4 Main feeds or 2-4 subdistribution
feeds (2 main or 2 subdistribution feeds
per BCMS)
Monitored with-Split-core 5-250A CTs for ABCN-Split-core 5A CT for G
CT branch circuit cable harnesses
21 BC connectors; 5, 10, 15, 20 ft. lengths
CT main or subdistribution circuit cable
harnesses
ABCNG connectors; 5, 15, 10, 20 ft. lengths
WaveStar Color Monitor, a 7-inch color
touchscreen display
Optional; display can monitor 20 downstream BCMS devices, such as panelboards
Setup connection
USB 2.0 A-B high-speed cable
Enclosure
Weight (without cables)
Approx. 11 lbs. or 5 kg.
Dimensions
20"W x 10"H x 6”D (51 cm x 25 cm x 15 cm)
Enclosure rating
NEMA 1
Network Communications
Protocol
Modbus RTU via RS422/485;
2-wire or 4-wire (jumper selected)
Protocol options upstream from monitor
Modbus RTU,
Modbus TCP/IP,
SNMP
Modbus address range
1 to 247
Baud rate
9600
Parity
Odd, even, or none
Communication format
8 data bits, 1 start bit, 1 stop bit
Electrical Characteristics
Input current rating
2.0A @ 115 VAC
Input voltage
/- 10%, 3-phase +n ground
Input frequency
60Hz +/-10%
Summary of Contents for PDI JCOMM
Page 1: ...p n P 164001107 Revision 01 Installation and Operation Manual Eaton PDI JCOMM Enclosure...
Page 4: ......
Page 12: ...2 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Safety...
Page 44: ...34 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Operation...
Page 46: ...36 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Service...
Page 48: ...38 Eaton PDI JCOMM Enclosure Installation and Operation Manual P 164001107 Rev 01 Bibliography...
Page 50: ...P 16400110701 P 164001107 01...