4 Configuring the device
4.1 Configuration of NZM basic devices
22
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
4.1 Configuration of NZM basic devices
4.2 MODBUS register
Following are the Modbus registers for the NZM…-XMC-MB measuring
modules.
Table 8: Configuration of the Modbus registers
Following is a description of the register assignments.
Variable
Register
Type
R = read/
W = write
a
page
Electrical parameters
0 - 95
R
Maximum values of the electrical parameters
96 - 191
R
Minimum values of the electrical parameters
192 - 287
R
Communications setup
1000 - 1002
R/W
Password setup
1050 - 1051
R/W
General configuration
1100 - 1105
R/W
Alarm 1
1150 - 1156
R/W
Alarm 2
1160 - 1166
R/W
Alarm 3
1170 - 1176
R/W
Alarm 4
1180 - 1186
R/W
Alarm 5
1190 - 1196
R/W
Alarm 6
1200 - 206
R/W
Mean value over time window
1250 - 1251
R/W
Special device configuration
1300 - 1400
R/W
Address and baud rate (broadcast)
3000 - 3002
W
Serial number
10000 - 10001
R
–
Expansion card 1
20000 - 20003
R/W
Expansion card 2
20010 - 20013
R/W
→
To activate changes, write TRUE to coil 2000.