List of event codes
Information – 248
7.5.2 UPS(HID) alarm log codes
7.5.2.1 Critical
Code
Severity
Active message
Non-active message
Advice
002
Critical
Internal failure
End of internal failure
Service required
004
Critical
Temperature alarm
Temperature OK
Check air conditioner
100
Critical
Rectifier fuse fault
Rectifier fuse OK
Service required
105
Critical
Input AC module failure
Input AC module OK
Service required
207
Critical
Bypass AC module failure
Bypass AC module OK
-
208
Critical
Bypass overload
No bypass overload
-
305
Critical
Rectifier failure
Rectifier OK
Service required
306
Critical
Rectifier overload
Rectifier OK
Reduce output load
308
Critical
Rectifier short circuit
Rectifier OK
Reduce output load
400
Critical
DCDC converter failure
DCDC converter OK
Service required
500
Critical
Battery charger fault
Battery charger OK
Service required
607
Critical
Battery test failed
Battery test OK
Check battery
60D
Critical
No battery
Battery present
Check battery
61B
Critical
Battery BMS fault
Battery BMS OK
Check battery
629
Critical
Battery voltage low critical
Battery voltage OK
Check battery
62B
Critical
Battery voltage high critical
Battery voltage OK
Check battery
62D
Critical
Battery charge current low critical
Battery charge current OK
Check battery
62F
Critical
Battery charge current high critical
Battery charge current OK
Check battery
631
Critical
Battery discharge current low
critical
Battery discharge current OK
Check battery
633
Critical
Battery discharge current high
critical
Battery discharge current OK
Check battery
This table applies to all UPS except to the 9130 UPS.
To retrieve Alarm logs, navigate to
section and press the Download alarms button.
Below codes are the one to be used to add "Exceptions on events notification" on email sending configurations.
Some zeros maybe added in front of the code when displayed in emails or logs.
Summary of Contents for Network-M3
Page 1: ...UPS Network Management Card Network M3 User s Guide English 10 27 2023...
Page 2: ......
Page 10: ...Table of Contents 10 Applicable product Eaton UPS ATS...
Page 32: ...Home Contextual help of the web interface 32 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode...
Page 34: ...Home Contextual help of the web interface 34 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode...
Page 36: ...Home Contextual help of the web interface 36 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode...
Page 63: ...Protection Contextual help of the web interface 63 Example 2 Immediate OFF...
Page 64: ...Protection Contextual help of the web interface 64 Example 4 Custom Settings 1...
Page 120: ...Settings Contextual help of the web interface 120 3 7 6 3 SSH 3 7 6 4 SNMP 3 7 6 5 MQTT...
Page 287: ...Acronyms and abbreviations Information 287...
Page 294: ......