Default settings and possible parameters
Information – 219
7.3.2 Meters
Default settings and possible parameters - Meters
Default setting
Possible parameters
Meters/Logs
Log measures every — 60s
Log measures every — 3600s maximum
7.3.3 Sensors alarm configuration
Default settings and possible parameters - Environment Alarm configuration
Default setting
Possible parameters
Temperature
Enabled — No
Low critical – 0°C/32°F
Low warning – 10°C/50°F
High warning – 70°C/158°F
High critical – 80°C/176°F
Enabled — No/Yes
low critical<low warning<high warning<high critical
Humidity
Enabled — No
Low critical – 10%
Low warning – 20%
High warning – 80%
High critical – 90%
Enabled — No/Yes
0%<low critical<low warning<high warning<high
critical<100%
Dry contacts
Enabled — No
Alarm severity – Warning
Enabled — No/Yes
Alarm severity – Info/Warning/Critical
Summary of Contents for Network-M2
Page 1: ...UPS Network Management Card Network M2 User s Guide English 10 15 2020 2 0 5 ...
Page 2: ......
Page 24: ...Configuring Modbus Installing the Network Management Module 24 ...
Page 25: ...Configuring Modbus Installing the Network Management Module 25 ...
Page 26: ...Configuring Modbus Installing the Network Management Module 26 ...
Page 38: ...Home Contextual help of the web interface 38 3 2 7 1 3 Battery mode 3 2 7 1 4 Off mode ...
Page 40: ...Home Contextual help of the web interface 40 3 2 7 2 3 Battery mode 3 2 7 2 4 Off mode ...
Page 42: ...Home Contextual help of the web interface 42 3 2 7 3 2 Bypass mode 3 2 7 3 3 Battery mode ...
Page 64: ...Protection Contextual help of the web interface 64 Example 2 Immediate OFF Example 4 Custom ...
Page 65: ...Protection Contextual help of the web interface 65 Settings 1 ...
Page 261: ...Acronyms and abbreviations Information 261 ...
Page 268: ......