IM02602002E
www.eaton.com
Page
5-1
MP-3000
SECTION 5 - PROGRaMMING ThE MP-3000
5.0 General
You can change MP-3000 settings in the Program mode. Before
changing settings, read this entire section, as well as Section 9 - Ap-
plication and Settings, for a full understanding of the settings and the
relay functions they control. This section summarizes the functions
of all of the settings. Section 9 provides more detailed engineering
explanation for selected settings that require it.
Open the front panel security door, and press the Prog(ram) pushbut
-
ton to place the MP-3000 into the Program mode (see Figure 4.1).
Table 4.3 can be used as both a guide and a worksheet for program
-
ming. The Page and Line pushbuttons permit the User to navigate
through the Program mode. The Value pushbuttons allow the setting
values to be changed.
To restore the default settings, use the file “MP3000defaultsCV1.set”
and download the settings using PowerPort and the front panel RS-
232 connector.
An MP-3000, which is protecting a running motor, can only be re
-
programmed after pressing the Prog pushbutton, pressing the Page
pushbutton 12 times, and pressing the Line pushbutton 6 times. Refer
to Section 5.12.6.
The MP-3000 continues to protect the motor with its prior settings as
the values are manipulated in the Program mode. Changes to the
settings do not take effect until the Prog button is pressed a second
time to exit the Program mode.
Make sure the motor is in a stable state before programming. If the
operating state of the motor changes during a programming operation,
the MP-3000 exits the program mode without actually making any of
the changes entered to that time. State changes include any transi
-
tion to start, run, stop, alarm, or trip.
In the following sections, the notation PnLm designates the setting on
page n, line m.
Note that if the unit is powered down for more than 30 days, the real-
time clock may need reset and the histories may need to be cleared.
Conditional Setting Ranges
Program settings have individual ranges and setting increments,
or selections, listed in Table 4.3. However, note that seven of the
settings have linked ranges. Because of this, it may be possible to
set unacceptable combinations of values during the programming
operation. If this error is made, pressing the Prog pushbutton does
not cause the MP-3000 to exit the programming mode. Instead, the
display indicates which setting is out of range, and the Help message
indicates the fix. Also, see individual descriptions for each of these
linked settings:
The ratio of Motor Full Load Amperes nameplate value
(FLA; P1L1) to Phase CT-ratio numerator (PCT, P1L5) must
be between 0.25 and 1.5. Both of these values are dictated
by the design of the protected motor. The error can be cor-
rected only by installing an appropriate current transformer
set for the motor. See FLA CT L and FLA CT H in Table 5-1;
refer to Section 5.1.5 for guidance on CT ratio selection.
The instantaneous over current trip setting (IOC, P3L4)
must be below (1,130 * PCT/ FLA)% or 1,600%, whichever
is less. See IOC OUT in Table 5-1.
The jam trip and alarm current levels (JMT, P3L6 and JMA,
P4L3) must be below (1,130 * PCT/ FLA)% or 1,200%,
•
•
•
whichever is less. See JAMT OUT and JAMA OUT in
Table 5-1.
The under load trip (ULT, P3L9) and alarm (ULA, P4L5)
levels must be greater than the programmed Stop Current
Threshold (STOP XX, P1L9). Remember that under load
trip and alarm functions are programmed as a percentage of
the FLA, while the Stop Current Threshold is programmed
as a percentage of the PCT. For comparison, multiply the
Stop Current Threshold by PCT/FLA.
A motor start is declared when the current is initially seen
with a magnitude greater than 30% of FLA (see Section
9.2.1). Make sure that the Stop Current Threshold is less
than this value. Remember the Stop Current Threshold is
programmed as a percentage of the PCT. For comparison,
multiply the Stop Current Threshold by PCT/FLA. This
number must be less than 30%.
The Motor Start Transition Current Level (TRNC, P5L5)
must be greater than the programmed Stop Current
Threshold. Remember that the TRNC is programmed as
a percentage of FLA, while the Stop Current Threshold is
programmed as a percentage of the PCT. For comparison,
multiply the Stop Current Threshold by PCT/FLA.
CaUTION
fLa IS a fIXED PROPERTy Of ThE MOTOR. SELECT a CT
WhOSE RaTIO IS SUITaBLE fOR ThIS MOTOR.
Viewing Settings
Most of the following settings can be viewed without accessing the
Prog button. To view the settings, use the View Setting display mode
button.
Note that certain settings without logical display values are not visible
in the View Setting mode. These are on setting pages 12, 13, and 14,
and are indicated by dashes in the Factory Default column of Table
4.3. They include testing settings and time values. Check the setting
of the calendar/clock using the Monitor Tim(e) page of the Monitor
Mode.
5.1 Page 1, SP MOTOR, Settings P1L1 to P1L8
These settings, which are motor constants, are usually obtained from
the motor nameplate or manufacturer-supplied data. They must be
correct for the MP-3000 to adequately protect the motor.
5.1.1 Setting P1L1, full Load amperes (fLa)
FLA is set to the maximum stator continuous RMS current in the
primary (actual motor winding) amperes in each phase. The motor
nameplate or manufacturer’s data provides the value of this setting.
NOTE:
Do not vary the FLA setting from motor nameplate value, even
if the motor has a service factor different from 1.0. See UTC,
P1L4 for the consideration of the service factor.
CaUTION
MaNy Of ThE PROTECTION fUNCTIONS Of ThE MP-3000
INCLUDING ThE MOTOR ThERMaL PROTECTION aLGORIThM,
USE ThE fLa SETTING VaLUE TO CaLCULaTE TRIP POINTS. If
ThE USER ENTERS aN INCORRECT SETTING, MaNy PROTEC
-
TION fUNCTIONS May NOT OPERaTE aS DESIGNED aND ThE
MOTOR May BE DaMaGED.
•
•
•
Summary of Contents for MP-3000
Page 1: ...IM02602002E www eaton com IM02602002E Rev E MP 3000 Motor Protection Relay ...
Page 18: ...IM02602002E Page 4 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 32: ...IM02602002E Page 4 20 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 54: ...IM02602002E Page 6 10 www eaton com MP 3000 Figure 6 7 Typical AC Supply and URTD Wiring ...
Page 55: ...IM02602002E www eaton com Page 6 11 MP 3000 Figure 6 8 Alternatives for Discrete Input Wiring ...
Page 60: ...IM02602002E Page 7 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 71: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 1 Rotor Temperature Tracking ...
Page 72: ...IM02602002E Page 9 www eaton com MP 3000 Figure 9 2 Motor Protection Curve ...
Page 73: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 3 Underload Jam Protection Curve ...
Page 76: ...IM02602002E Page 9 12 www eaton com MP 3000 Figure 9 6 Motor Start and Run Cycles ...
Page 79: ...IM02602002E www eaton com Page 10 MP 3000 Figure 10 1 PONI Communications Module ...
Page 90: ...IM02602002E Page 12 www eaton com MP 3000 This Page Intentionally Left Blank ...
Page 99: ...www eaton com MP 3000 IIM02602002E This Page Intentionally Left Blank Page 13 9 ...