Mounting
15
02/09 AWB2723-1612en
Potential Relationship between the Components
The entire SmartWire-Darwin system operates on a common
supply voltage. Provide a common star point for the earth
wiring. In this way the various slaves in the SmartWire-
Darwin system will not be electrically isolated from one
another. The field bus and the SmartWire-Darwin system are
electrically isolated from one another.
Connection SmartWire Darwin
X
Connect the SmartWire-Darwin network via the 8-pole
SmartWire-Darwin cable. To do so use the SmartWire-
Darwin cable SWD-4-100LF8-24 and the relevant blade
terminal SWD-4- 8MF2 or prefabricated cables of the type
SWD-4-(3/5/10)F8-24-2S.
j
Warning!
Switch off the power supply, if you are reconnecting slaves
in the SmartWire-Darwin system or reconnecting the
ribbon cable connection. Otherwise the SmartWire-
Darwin slaves can be destroyed!
j
Warning!
The gateway has protection against polarity reversal for
the 24-V-DC-POW supply. However, if the gateway is
connected via the serial interface to an earthed device (for
example to a PC), the gateway can be destroyed, if the
polarity of the power supply is reversed!