background image

Menvier30 

Page 3 

2. Before You Begin 

Preparation 

Before installation you should carry out a survey 
of the site. You need to know how many and what 
kind of detectors will be monitored by the control 
unit. You also need to assess where any radio 
expanders must be placed in order to receive 
radio signals from their detectors successfully. 

Radio Site Survey 

If you intend to fit radio expanders you should 
conduct signal strength tests. 

Eaton’s Security 

Business produces the Scantronic 790r hand held 
signal strength meter and 734r-01 test transmitter 
for this purpose. Please read the 790r manual for 
details.  

Please be aware of the following: 

 

The 790r signal strength meter readings 
should be used only as an guide when initially 
checking the site. 

 

A reading of four green LEDs or higher 
indicates an acceptable signal strength. 

 

Once you have installed the alarm system you 
should put the control unit in the Installer test 
menu and test the received signal strength 
from each radio transmitter. 

 

A signal strength reading of two or more units 
by the control unit from each transmitter 
should provide reliable operation in the 
installed system. (

Note:

 if you take the signal 

strength using 

Eaton’s Security Business 

Downloader or the web server while the panel 
is in user mode then the minimum acceptable 
signal strength is four units. Ensure that the 
control unit is in Installer mode when reading 
signal strengths remotely.) 

 

When you record the signal strength readings 
for later inspection, you should record the 
readings taken from the control unit of the 
installed system while it is in the Installer 
Menu. 

Please be aware that the signal strength received 
from a transmitter can change after installation 
because of local environmental changes. For 
example, users switching on laptops nearby, or 
moving metal cabinets from their original position 
can all affect the signal from a transmitter. Please 
read 

Eaton’s Security Business publication 

”Guidance Notes for Wireless Alarm System 
Installations” obtainable from 
www.coopersecurity.co.uk for more information 
about the factors affection radio signal strength. 

Siting the Control Unit and Wired Zone 
Expanders 

Do site the unit: 

 

Upright, battery at the bottom. (This does not 
apply to the wired zone expander.) 

 

Within a protected zone. 

Do NOT site the unit: 

 

In the entry or exit zones, or outside the area 
covered by the alarm system. 

 

Next to electronic equipment, particularly 
computers, photocopiers or other radio 
equipment, CAT 5 data lines or industrial 
mains equipment. 

 

Where the cable run will exceed the capacity 
of the bus, see page 12. 

Siting Keypads 

Do site the keypad: 

 

Within the area protected by the alarm 
system. 

 

At a convenient height and location for the 
user. 

 

Out of sight of potential intruders. 

 

Where the cable run will exceed the capacity 
of the bus, see page 12. 

Do NOT site the keypad: 

 

Next to electronic equipment, particularly 
computers, photocopiers or other radio 
equipment, CAT 5 data lines or industrial 
mains equipment. 

 

Where the cable run will exceed the capacity 
of the bus, see page 12. 

If fitting two or more keypads make sure that you 
place the keypads more than one metre apart 
from each other, or from any other type of prox 
reader. (At less than one meter separation the 
proximity tag readers  will interfere with each 
other.) Remember not to place keypads or 
external prox readers on opposite sides of the 
same wall. 

If you intend to fit external prox reader KEY-EP to 
a KEY-KPZ01/KP01, then do not site the external 
prox reader itself closer than one meter to any 
other keypad or other type of prox reader. 

Siting Wireless Zone Expanders 

Do site the unit: 

 

Upright. 

 

Within a protected zone. 

 

As high as possible. However, do make sure 
that the unit is on a similar level to the 
transmitters or receivers. 

 

More than 10m from another radio expander. 

Summary of Contents for MENVIER30

Page 1: ...Menvier30 Security System Installation Guide Issue 2...

Page 2: ...ing you to potential problems or hazards Each of these are marked by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not da...

Page 3: ...eakers 21 Step 5 Connect Control Unit to Mains 21 Mains Cabling 21 Step 6 Connect Wired Zones 21 Four Wire Closed Circuit Connections 21 Two Wire Closed Circuit Connections 22 Fully Supervised Loop Co...

Page 4: ...Menvier30 Page iv This page is intentionally blank...

Page 5: ...a passive infra red detector smoke detector external siren 4 button remote control and remote radio keypad This control unit is designed and approved to be used as part of a Security Grade 2 system Zo...

Page 6: ...of the Installer s programming menu please read Menvier30 40 100 300 Engineering Guide available from www coopersecurity co uk Installer Programming Interface Once fitted and powered up you can progr...

Page 7: ...metal cabinets from their original position can all affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtai...

Page 8: ...n metal or conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the Menvier30 its expanders and keypads have been tested...

Page 9: ...g by output connectors 4 Tamper switch connector 5 ADSL filter pins 6 On board communicator connections 7 Off hook LED 8 USB socket Mini B 9 Sockets for plug on module 10 Loudspeaker Bell and Strobe c...

Page 10: ...envier30 Page 6 1 Built in communicator telephone line connector 2 Siren and strobe 3 Loudspeaker 4 Bus cable connector 5 Output transistorised 6 Aux power 7 Wired zone connectors Figure 4 Control Uni...

Page 11: ...To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing...

Page 12: ...push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the front out from the back bo...

Page 13: ...r KEY EP Terminals for zones 4 Sounder volume control 5 Connector for data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing not used 6b LED functions and RS485 bus termi...

Page 14: ...ker connectors 19 Outputs Figure 15 EXP W10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper sw...

Page 15: ...able front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Louds...

Page 16: ...example system and would meet the Grade 2 requirements Note All current drawn from the Aux terminals 12V must be included in the overall calculation CAUTION Ensure that the system does not demand more...

Page 17: ...ain see Fig 18 In a star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper...

Page 18: ...80mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Reducing Voltage Drop Method 1 Double up the supply connections 12V a...

Page 19: ...ere must be enough space around this point to fit the supplied tamper shroud see Figure 21 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied from the factory with four plastic feet a...

Page 20: ...uring Screw When the PCB is in place connect the wires from the transformer to the 20Vac connector on the PCB 18 in Figure 3 Installing the Lid Back Tamper Figure 25 Lid Back Tamper Fit combined lid b...

Page 21: ...ontrol systems If you mount prox readers closer together than one meter including on the other side of walls then the two prox readers will interfere and may not work correctly Fitting Keypads Select...

Page 22: ...ng mode allows you to enable or disable the LEDs in the ABCD keys and the Navigation key It is possible to enter keypad programming mode when the keypad is not connected to a control unit but simply p...

Page 23: ...any fault reports MENU STATUS FLT LED 4 Leave local programming mode and save your changes see below To Leave Local Programming Mode and Save Changes EITHER Press OR Close the keypad tamper The keypad...

Page 24: ...gure 32 shows the wiring connections at the keypad Figure 32 Connecting the External Prox Reader Tone Volume All Keypads To alter the volume of non alarm tones from the keypad adjust the keypad sounde...

Page 25: ...tions must be carried out by a qualified electrician and must comply with the current local regulations e g IEE Mains Cabling Note To avoid mains interference the mains cable must enter the control un...

Page 26: ...r you can mimic the setting by using 4k7 2k2 4 wire CC zone wiring option and then connecting the detector to the alarm terminals and placing a short across the tamper terminals Fully Supervised Loop...

Page 27: ...igure 43 shows the connections required Figure 43 Wiring Two Detectors per Zone FSL Figure 44 shows an example of wiring double doors with two door contacts to one FSL zone Each door contact is a reed...

Page 28: ...ng Bell Tamper unnecessarily Wired Outputs on Expanders Each EXP W10 wired expander provides connections for up to four transistor driven outputs Each output has a maximum rating of 500mA but note tha...

Page 29: ...as described above Figure 49 Wiring TR from External Sounder to a Zone on the Expander Remote Loudspeakers Optional If you wish to add a 16 Ohm wired Loudspeaker unit then connect it as shown in Figur...

Page 30: ...th or without secondary proceed indication Note The built in communicator is not suitable for connection as an extension to a pay phone or to 1 1 carrier systems Approval The built in communicator is...

Page 31: ...the authorised maintainer To connect the telephone line see Figure 52 i Using a two core telephone cable strip off 5mm and feed the cable through one of the entries marked 10 in Fig 2 in the rear of...

Page 32: ...s present and 0V when the fault is absent Tell Back Input This input is designed to allow a plug by communicator to indicate to the control unit that the user can reset the system after a system tampe...

Page 33: ...that the sudden noise does not startle you and cause a fall 1 Apply mains power to the control unit The keypads and internal sounder may give an alarm tone The heartbeat LED on the control unit PCB se...

Page 34: ...s OK Two No communication over the bus in the last 10 seconds Three No bus address allocated to expander Four No poll request received from control unit in the last minute Transferring to Another Keyp...

Page 35: ...tive If you need to re enter the Installer Menu 1 Make sure the system is unset and showing the standby screen time and date 2 Key in the Installer access code The default Installer access code is 123...

Page 36: ...to display the desired wiring type on the bottom line of the display and then press to select it The system loads all defaults except for Access Codes and the Log The display briefly shows Followed b...

Page 37: ...screw NOTE It is possible for convenience to place links over tamper contacts to inhibit tamper alarm for example during installation or if the unit is installed inside a larger tampered housing Beca...

Page 38: ...ay Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation Confirmation Mode Basic DD243 BS8243 Confirmation time 7 After entry 7 Entry keypad lock 7...

Page 39: ...sabled 15 Appears only when Dynamic Test Call is disabled 16 Appears only if EXP PSU is fitted 17 Appears only if Report Mode Fast Format AND Confirmation Mode Basic 18 Shows None on Menvier30 If no c...

Page 40: ...employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its sounder Once you have found the bus device you can silence...

Page 41: ...ithout power Internal Clock 10 minutes over one year depending on the accuracy of the mains supply frequency User Codes 50 plus installer code Remote controls 50 one per user HUA Alarms 50 one per use...

Page 42: ...e range 10 0 5V to 13 8V 12V Aux output voltage range 10 0 5V to 13 8V 12V Bell output voltage range 10 0 5V to 13 8V Max p to p ripple voltage 0 5V Standby Battery 12V 7Ah sealed lead acid not suppli...

Page 43: ...726rEUR 60 Short range hand held HUD Detectors 713rEUR 00 Pet tolerant PIR 714rEUR 00 PIR Transmitter Small case 720rEUR 00 Smoke Detector Transmitter 734rEUR 00 01 CC FSL Door Contact Transmitter whi...

Page 44: ...www coopersecurity co uk Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number 1...

Reviews: