Effective June 2009

Instructional Leaflet 

IL2C12769H07 

Remote latch check switch (LCS) for

Magnum low voltage circuit breakers

 warning

(1) Only qualified electrical persOnnel shOuld 

be permitted tO wOrk On the equipment.  

(2) always de-energize primary and  

secOndary circuits if a circuit breaker  

cannOt be remOved tO a safe wOrk lOcatiOn. 

(3) drawOut circuit breakers shOuld be 

levered (racked) Out tO the discOnnect  

pOsitiOn. 

(4) all circuit breakers shOuld be switched  

tO the Off pOsitiOn and mechanism springs 

discharged. 

failure tO fOllOw these steps fOr all  

prOcedures described in this instructiOn  

leaflet cOuld result in death, bOdily injury,  

Or prOperty damage.

Section 1: General information

A latch check switch (LCS) indicates when the 

circuit breaker is “ready to close” (

Figure 1

). The 

internal version of the LCS is wired to the spring 

release. It will not permit activation of the spring 

release until the circuit breaker is fully charged and 

the trip latch is reset. 

Required tools

• 

1/4-inch drive socket

• 

10 mm socket

Kit parts identification

Refer to 

Figure 1

 for visual identification of the 

contents of kit.

Figure 1. Contents of Kit

Section 2: Installation of internal 

remote LCS

To install the LCS, proceed with the following  

six steps:

Step 1: 

Remove the front cover by unscrewing 

the hex head captive bolts (four for three-pole, 

six for four-pole) that join the cover to the breaker 

housing using a 10 mm 1/4-inch drive socket. 

Then hold the charge handle down at about a  

45-degree angle to pull off the cover. 

Figure 2. Step 1

LCS (internal 

version shown)

Mounting Bolts