3
Product overview
EATON ICUBE 2.0
UM.ICUBE2.0.SG.0822 August 2022 www.eaton.com
1.2 System assembly
Figure 1 .5
System assembly diagram (Take 1 + 6 as an example)
System configuration table:
Model
*Load
capacity
Number of
cabinets
UPS
Air-conditioning Module
PDU
EMSRE3K24U-EA
2.4KW
1
EMUPS9PX3K
–
PDME-6K
Basic type IEC32A-12x C13, 4 x C19 (1PCS)
EMSRE6K24U-EA
4.8KW
1
EMUPS9PX6K
–
PDME-6K
Basic type IEC32A-12x C13, 4 x C19 (1PCS)
EMSRE3K42U-EA
2.4KW
1
EMUPS9PX3K
–
PDME-6K
Basic type IEC32A-20x C13, 4 x C19 (1PCS)
EMSRE6K42U-EA
4.8KW
1
EMUPS9PX6K
–
PDME-6K
Basic type IEC32A-20x C13, 4 x C19 (1PCS)
EMSRS3K42UA-EA
*2.0KW*
1
EMUPS9PX3K
E02A
PDM-6K
Basic type IEC32A-20x C13, 4 x C19 (1PCS)
EMSRS6K42U-EA
3.5KW
1
EMUPS9PX6K
E04S/ EW06
PDM-6K
Basic type IEC32A-20x C13, 4 x C19 (1PCS)
EMSRS10K42U-EA
3.5KW
1
EMUPS9PX11K
E04S/ EW06
PDM-10K
Basic type IEC32A-20x C13, 4 x C19 (1PCS)
EMMRS10K1/2-EA
*7KW
1+2
EMUPS9PX11K
E08S/EW10
PDM-10K
Basic type IEC32A-20x C13, 4 x C19 (5PCS)
EMMRS(2)10K1/2-EA *7KW
1+2
EMUPS9PX11K*2 E08S/EW10
PDM-2x10K Basic type IEC32A-20x C13, 4 x C19 (5PCS)
EMMRS20K1/4-EA
*14KW
1+4
9SX20KPM
E08S/EW10 *2
PDM-20K
Basic type IEC32A-20x C13, 4 x C19 (9PCS)
EMMRS(2)20K1/4-EA *14KW
1+4
9SX20KPM*2
E08S/EW10 *2
PDM-2x20K Basic type IEC32A-20x C13, 4 x C19 (9PCS)
EMMRS20K1/6-EA
*14KW
1+6
9SX20KPM
E08S/EW10 *2
PDM-20K
Basic type IEC32A-20x C13, 4 x C19 (13PCS)
EMMRS(2)20K1/6-EA *21KW
1+6
9SX20KPM*2
E08S/EW10 *3
PDM-2*20K Basic type IEC32A-20x C13, 4 x C19 (13PCS)
ote:
N
The load capacity of the model marked with an asterisk (*) need to be derated to 90% when the cabinets’
ambient temperature is 30-40° C.
When using three-phase power, pay attention to the principle of evenly distributing the loads of each phase
and try to distribute the load evenly in each cabinet.