14
Installation
EATON ICUBE 2.0
UM.ICUBE2.0.SG.0822 August 2022 www.eaton.com
3.2.2 Electrical connection for the cooling unit(applicable to two coolers or above):
Connect the cooling power cables which are pre-assembled on the top of the IT cabinet to the coresponding
terminals label A/C at the rear of the PDM.
Attention should be paid to the corresponding labels, L L; N N; PE PE, see the figure: 3 .6 below:
Figure 3 .6
3.2.3 Communication to the cooling units
3.2.3.1 Data and control connections
Connect the network cable (identified by AC PORT) left on the top of air conditioner cabinet 1 to the POR1 PORT
at the rear of cooling unit 2 in the following figure: 3.7 & 3.8.
Connect the network cable left on the top of air conditioner cabinet 2 to the POR1 port at the rear of cooling
unit 3 in the following figure: 3.7 & 3.8.
Figure 3 .7