56
Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual 164000639—Rev 03
CAUTION
The shelf life for the batteries installed in the IBC is 6 months from the date code on the battery. The recharge
date is also stated on a label inside the IBC.
Failure to recharge the batteries before the expiration of the shelf life will result in reduced discharge time,
shorter float service life, and will void the warranty.
77..22..22
EEnnvviirroonnm
meennttaall aanndd S
Saaffeettyy S
Sppeecciiffiiccaattiioonnss
Operating Temperature
The battery cabinet is rated for operation in up to a 40°C (104°F) ambient
temperature.
The batteries are rated for a 25°C (77°F) ambient temperature to extend their useful
life.
Transit Temperature
-25°C to 60°C (-13°F to 140°F)
Recommended Eaton PWHR12200W4FR or CSB HRL12200WFR
Battery Transit: -20°C to 50°C (-4°F to 122°F)
Storage Temperature
-25°C to 55°C (-13°F to 131°F)
Recommended Eaton PWHR12200W4FR or CSB HRL12200WFR
Battery Storage: -20°C to 30°C (-4°F to 86°F)
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Transit Altitude
15000m (49213 ft)
Ventilation
Convection
Relative Humidity (operating and
storage)
5 to 95%, noncondensing
Acoustical Noise
Not applicable
Safety Conformance
UL1778 5
th
edition
Agency Markings
cULus
EMC (Class A)
FCC Part 15 Class A and 62040-2 C3