Capitole 40
66 1991.901 G01 002
•
Turn each operating panel in such a way that it slides
easily through the designated opening in the door, from
the inside to the outside.
•
Push each operating panel back into the correct
position in the opening in the door; the interlock cams
will now click around the edges of this opening.
•
Secure the operating panel cable bundle(s) using the
bundle clips that are present in the door.
•
Connect the outgoing main power cables and mount
the shielding plate in the cable compartment.
•
Plug the auxiliary power plugs (at the correct position)
into the terminal strip that protrudes into the cable
compartment (also connect the auxiliary power
connections with the auxiliary bars, if present).
•
Then switch on all MCCBs in and close the door of the
compartment concerned and the cable compartment
door.
3.4.3.3
Adding a plug-in unit
Panels that have empty spare compartments allow for the
subsequent addition of plug-in units. Such spare
compartments have a blind door and a shielding plate at
the cable compartment side.
Figure 3-42
Adding a plug-in unit for distribution at an IP31
ventilated panel
•
Open the blind door of the spare compartment and the
upper compartment blind door.
W
ARNING
Ensure that the plug-in unit circuit breaker and/or
the switch-disconnector are in the OFF position.
•
Loosen the two blind door hinge screws until the door
can be removed and then
•
remove the door.
Figure 3-44
N
OTE
The uppermost hinge screw of the blind door is
also the bottommost hinge screw of the upper
door.
•
Open the cable compartment door and remove the
shielding plate from the spare compartment concerned.
•
Place the extension unit in the spare compartment.
Ensure that the MCCB or switch-disconnector is in the
OFF position. Secure the unit with the four bolts.
•
Check that the outgoing main power circuit is isolated.
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...