Capitole 40
50 1991.901 G01 002
3.4.2 Modification of a withdrawable version
of the assembly
General
This paragraph describes the modification of the cubicle
layout with outgoing feeders in the withdrawable version.
The standard version of a cubicle consists of sixteen units
each being 125 mm high and 500 mm wide.
From these units a cubicle may be constructed with
compartments each provided with draw-out units of 1x125
mm up to a maximum of 16.
If it is desired the layout of a cubicle can be changed. One
standard (size 125 mm) compartment can be split into two
smaller sized drawers.
The modification of the cubicle layout can be done in a
simple way. There are four possibilities:
a.
Changing a number of small compartments into one
large compartment, see below.
b.
Changing one large compartment into a number of
small compartments, see page 51.
c.
Changing one split-up compartment with two or
three draw-out units into one compartment with one draw-
out unit, see page 51.
d.
Changing a compartment with one draw-out unit
into a split-up compartment with two or three draw-out
units, see page 57.
a.
Changing a number of small compartments
into one large compartment
•
Remove the doors of the compartment concerned by
removing thehexagonal socket-head bolts from the
hinges.
•
Then remove the insulated screening-plate between the
cable-compartment and the draw-out unit compartment
by turning the quick-locking device through 90°.
•
Remove the secondary wiring and the main cable.
•
The horizontal dividing-plate can be slid out after the
twofastening bolts in the frontal upright have been
removed.
•
The large door and the screening-plate may then be
fitted.
b.
Changing one large compartment into a
number of small compartments
•
Remove the large door and screening-plate as
described above.
•
Fit the necessary horizontal dividing-plates.
A
TTENTION
Ensure that the horizontal dividing-plates are
positioned in the correct slots, at the back of the
cubicle.
•
Fit the necessary doors and screening-plates.
Summary of Contents for Holec Capitole 40
Page 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Page 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Page 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Page 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Page 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Page 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Page 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Page 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Page 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Page 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Page 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Page 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Page 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Page 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Page 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Page 99: ...Capitole 40 1991 901 G01 002 99...
Page 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Page 101: ...Capitole 40 1991 901 G01 002 101...