Section 1: System installation and design
Optional functions as per EN54 P2&4
The Panel is Designed to the requirements to EN54 Parts 2 & 4 including all the
following options which can be selected as required .
Panel outputs
Panel Sounders: (OPTION 7 .8 EN54 PT 2) .
Two Sounder outputs are provided . ONLY polarised equipment should be used .
Ensure the polarity of the connections are observed at all times and end of line
device are fitted for correct operation .
The total alarm load across all sounder outputs = 1 .5 Amp .
All outputs are fused with 1 .6 Amp Glass fuse Alarm devices should be spread
equally across the 2 sounder circuits .
WARNING
Do not exceed the rated output current .
Output to fault warning routing equipment (Option 9 .4 .1C EN54 pt 2)
This output, which is fused and monitored using 2k0 end of line resistor, is used
for the transmission of fault signals to fault warning routing equipment This output
is monitored using 2k0 end of line resistor and it current limited to 30 mA . Under
normal condition it operates by providing 12vdc which can be connected directly to a
12v auxiliary device( relay) .It is current limited to 30 mA .
Under fault conditions or even if the Panel is powered down, this output will be
switch to O volts . Ensure the polarity of the connections is observed at all times and
end of line resistors ( 2K0 5% ) are fitted for correct operation .
Delays to outputs (Option 7 .11 of EN54 pt 2)
The Panel has the option to delay the operation of panel sounders, the fire routing
equipment output and the fire protecting Equipment . This delay is selectable using
the site installer download software . The delay is configurable in increments of 1
minute up to a maximum of 10 minutes . This delay can be enabled and disabled at
access level 2 .
The Panel has the facility for a specific call point to override this delay by
programming this call point via an input interface to provide an evacuate signal using
site Installer .
Coincidence detection (Option 7 .12 of EN54 pt 2)
The Panel has the facility to inhibit the operation of the output sounders, Output
to Fire routing equipment and the output of the fire protecting equipment until
one more confirmatory signals are received from different zones . This feature is
programmable using Site Installer Software .