Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
67
Table 29. Typical Alarm Conditions (Continued)
32
BATTERY TEST
FAILED
A
Batteries may need
replacement soon
Normal
Replace Batteries soon
33
FUSE FAILURE
A
Hardware failure
Off or Battery Mode
Call Eaton Service
34
FAN FAILURE
A
Fan(s) not working
Normal
35
SITE WIRING
FAULT
A
Input wiring L-N got
reversed
Normal (if previous state
was ON) Will not turn on if
previous state is Standby
Shut UPS and Input Circuit
Breaker off. Check input
wiring and correct if L and N
got reversed.
36
BATTERIES
DISCONNECTED
A
Battery Breaker Turned
Off. Battery wires came
loose or Battery Voltage
too low.
On with Alarm
Should initiate graceful
shutdown for load. And then
call Eaton Service.
38
PRECHARGE
FAILED
A
UPS not turning on
Off
Call Eaton Service
39
CHARGER ON
Status
Charger is ON
Normal
Nothing.
40
UPS ON BATTERY
Status
UPS in Battery Mode
Supporting Load on Battery
Nothing.
41
UPS ON NORMAL
Status
UPS in Line Mode
Supporting Load
Nothing.
42
BATTERY TEST IN
PROGRESS
Status
UPS in Line Mode
Supporting Load
Nothing.
45
INVERTER
OVERTEMPERA-
TURE TRIP
A
Inverter heatsinks too
hot
Off
Check Fans. If they are
blocked, unblock them. If
they are fine, call Eaton
Service.
46
OUTPUT
OVERLOAD TRIP
A
Load exceeded
Level 1 105%
Level 2 110%
Level 3 125%
Off
Reduce Load and turn UPS
on again.
47
POWER_SUPPLY
5 VOLT FAULT
A
Hardware failure
Off
Call Eaton Service
48
CONTROL POWER
OFF
Status
UPS turned off
Off
Nothing.
49
STANDBY
COMMAND
Command
UPS turned off
Off
Nothing.
52
CHARGER
FAILURE
A
Charger failed
On with charger fail alarm
Call Eaton Service
53
UPS ON
GENERATOR
N
On-Generator signal
activated by customer
Normal but on Generator
Nothing if this was
intentional. If unexpected,
check if the signal at the
rear of the UPS got
activated by mistake.
56
AMBIENT
OVERTEMPERA-
TURE
A
Ambient exceeds max
temperature of 70C
On
Make sure UPS is in an
ambient temperature <=
40C. Check Fans.