Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
65
Table 29. Typical Alarm Conditions (Continued)
If problem persists, call
Eaton Service
4
INVERTER
OVERTEMPERA-
TURE
A
Inverter Heatsink
temperature exceeded
max rating
UPS was supporting load in
Battery Mode, but, after
some time, the Inverter
Heatsink temperature
exceeded the max limit and
the UPS dropped the load
and switched to Keep-Alive
Mode
Check if the Fan(s) is (are)
ON . Check Input Circuit
Breaker and turn it ON. Call
Eaton Service if problem
persists.
5
INVERTER
OUTPUT OVER
CURRENT
A
UPS overloaded
Load exceeded max rating
Check to see if the load
exceeds the max rating of
the UPS. Reduce Load and
see if the UPS is working as
expected. Call Eaton Service
if problem persists.
6
BATTERY
CURRENT LIMIT
A
Overloaded
Overload on Inverter
Reduce Load and check if
the Alarm goes away. If it
doesn’t, and the problem
persists, please call Eaton
Service.
7
EEPROM FAILURE
A
Invalid checksum while
reading the EEPROM
UPS will remain in the INIT
state, unable to start until
the eeprom is reset
Call Eaton Service
8
SHUTDOWN
IMMINENT
A
UPS Supporting Load
with Battery but Battery
Voltage has reached a
very low level and the
UPS is about to drop
load and switch to
Keep-Alive mode
UPS supporting load on
Battery
Shut Load down gracefully
(typically load server
software should do this if it
reads this A code from the
UPS).Check if Input Circuit
Breaker is Off – and turn it
ON if input measures ok
9
BATTERY LOW
A
UPS Supporting Load
with Battery but Battery
Voltage has reached a
low level
UPS supporting load on
Battery
Shut Load down gracefully
(typically load server
software should do this if it
reads this A code from the
UPS).Check if Input Circuit
Breaker is Off – and turn it
ON if input measures ok
10
UTILITY NOT
PRESENT
N
Input AC Voltage not
available
UPS supporting load on
Battery
Check input Circuit Breaker
Check input voltage ,If it is
good, turn the circuit
breaker ON. If problem
persists, call Eaton Service.
11
INPUT
SWITCHGEAR
CLOSED
Status
Indicates Relays turning
on (closing) on AC Board
Normal Mode
Nothing.
12
BATTERY DC
OVER VOLTAGE
A
Battery Voltage
exceeding max limit
Charge Mode supporting
Load
Power Cycle. If problem
persists, turn unit off and
call Eaton Service.