Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
Table 19. Parameter List (Continued)
Parameter
Number
Sample / Default
Password Level
Range
Description
7
“07 V Batt 48.1 V”
Service
0.0 – 175.0
Measured average DC volts of the UPS
battery. Programming changes an internal
setting to calibrate reading.
8
“08 Freq 60.00 Hz”
No Change
Allowed
47.00 – 63.00
Line input frequency when line is OK. Line
output frequency otherwise. Display
parameter only, unprogrammable.
9
“09 RunTime 12 m”
No Change
Allowed
0 – 9999
Approximate runtime presently available to
the load during inverter operation. Display
parameter only, unprogrammable.
10
“10 Date 01/01/20”
User
01/01/00 – 12/
31/99
Today’s date in Mo/Dy/Yr format. Date is
set to last known date whenever UPS is
turned on. UPS internally sets years
between 2000–2099.
11
“11 Amb Temp 23 C”
No Change
Allowed
–63 – 193
Temperature of air around logic board.
12
Reserved
13
Reserved
14
14 Xfmr Temp 28 C
No Change
Allowed
–63 – 193
Transformer temperature. The FerrUPS will
alarm if this value is too high. This
parameter is only for models that monitor
transformer temperature; for other models,
this parameter will always show -63° C.
15
“15 Unit ID “Network
#1 UPS”
No Change
Allowed
0 – 20 chars
Provides user configurable identification
string of the UPS. Usually used in network
configurations.
16
“16 FullLoad% 75”
No Change
Allowed
0 – 150
FullLoad% = (VAOut/VALimit) * 100. Display
parameter only, unprogrammable.
17
“17 Watts 374”
No Change
Allowed
0 – 15000
Watts being used by load. = Instantaneous
dot product of ACVoltsOut x ACAmpsOut.
(average power)
18
“18 PF 0.73 Lead” or
“18 PF 0.82 Lag” or
“18 PF 1.00 —”
No Change
Allowed
0.00 – 1.00
Power factor of user load. PF types: Lead,
Lag, Distortion or — (Indeterminate)
depending on load type. PF magnitude =
Watts / VA Out. The unit should always
display 1.00 — for loads < 25%
19
“19 VALimit 2200 VA”
No Change
Allowed
350 – 18000
Max allowable load in VA. Limit changes
depending on load type. For “Lead” or
“Dist” types the unit is prorated as: VALimit
= RatedWatts/PF.
20
20 ActiveAlm "Batt
Disconnected"
No Change
Allowed
N/A
It will scroll all Active alarms, each for 3
seconds. User can toggle scrolling by
pressing '0'. When scrolling is stopped,
pressing '1' will move to next event (older).