For more information visit:
www.EatonElectrical.com
Programming wiring
MN05013005E
204
You integrate a counter into your circuit in the form of a
contact and coil. The counter relay has different coils and
contacts.
Figure 106: EZD circuit diagram with high-speed incremental
encoder counter
Parameter display and parameter set for high-speed
incremental encoder counter:
In the parameter display of a counter relay you change
setpoint values and/or the preset value and the enable of the
parameter display.
Value range
The function block operates in the integer range from
–2147483648 to 2147483647.
Each pulse is counted twice.
Example: value at CI..QV>= 42000
The counter has counted 21000 pulses.
J
To prevent unpredictable switching states, use each coil of
a relay once only in the circuit diagram.
Use a counter input for the CF, CH, CI counters only once.
I 05---------------------------Ä CI01EN
I 06---------------------------Ä CI01RE
I 08---------------------------Ä CI01SE
CI01OF-------------------------Ä Q 01
CI01FB-------------------------Ä Q 02
CI01ZE-------------------------Ä Q 03
CI01CY-------------------------S M 94
CI01 +
>SH
>SL
>SV
QV>
CI01
High-speed incremental encoder counter function block
number 01
+
Appears in the parameter display
>SH
Upper setpoint
>SL
Lower setpoint
>SV
Defined actual value (Preset)
QV>
Actual value in RUN mode