Configuring the interface for the COM-LINK mode
For more information visit:
www.EatonElectrical.com
MN05013005E
103
to configure the stations which have an active power
supply.
X
Go to the EZD device that is the active station running the
serial interface.
Setting up the COM-LINK
X
Simultaneously press the
DEL
and
ALT
buttons while EZ
shows the Status display.
The System menu appears
Select the CONFIGURATOR menu option.
X
Press the
OK
button.
Select the COM... menu option.
X
Press the
Ú
button.
X
Press the
OK
button.
J
The following tasks are only possible in STOP mode.
Caution!
The EZD device can either run as a station on the EZ-NET
or as a station in a COM-LINK connection. Do not switch an
EZD device running as an EZ-NET station to COM-LINK. If
this is done on EZ-NET in RUN mode, the entire EZ-NET
network will be deactivated. There will be no further data
transfer.
Solution:
X
Deactivate the COM-LINK.
X
Re-enter the EZ-NET address.
X
Switch the power supply off and then on again.
X
Reconfigure the EZ-NET on station 1.
SECURITY...
SYSTEM...
MENU LANGUAGE
CONFIGURATOR...
NET..
COM...
LINK....