ADD-AMP capabilities
Table 11 . ADD-AMP capabilities of 60 Hz ratings
Rated
Volts
Rated
kVA
Load Current Ratings (A)
a
Regulation Range (Wye and Open Delta)
± 10%
± 8.75% ± 7.5%
± 6.25% ± 5%
Regulation Range (Closed Delta)
± 15%
± 13.1% ± 11.3% ± 9.4%
± 7.5%
2500
50
200
220
240
270
320
75
300
330
360
405
480
100
400
440
480
540
640
125
500
550
600
668
668
167
668
668
668
668
668
250
1000
1000
1000
1000
1000
333
1332
1332
1332
1332
1332
416.3
1665
1665
1665
1665
1665
5000
25
50
55
60
68
80
50
100
110
120
135
160
100
200
220
240
270
320
125
250
275
300
338
400
167
334
367
401
451
534
250
500
550
600
668
668
333
668
668
668
668
668
416.3
833
833
833
833
833
7620
b
38.1
50
55
60
68
80
57.2
75
83
90
101
120
76.2
100
110
120
135
160
114.3
150
165
180
203
240
167
219
241
263
296
350
250
328
361
394
443
525
333
438
482
526
591
668
416.3
548
603
658
668
668
500
656
668
668
668
668
667
875
875
875
875
875
833
1093
1093
1093
1093
1093
13800
69
50
55
60
68
80
138
100
110
120
135
160
207
150
165
180
203
240
276
200
220
240
270
320
414
300
330
360
405
480
500
362
398
434
489
579
552
400
440
480
540
640
667
483
531
580
652
668
833
604
664
668
668
668
Table 11 . (continued)
Rated
Volts
Rated
kVA
Load Current Ratings (A)
a
Regulation Range (Wye and Open Delta)
± 10%
± 8.75% ± 7.5%
± 6.25% ± 5%
Regulation Range (Closed Delta)
± 15%
± 13.1% ± 11.3% ± 9.4%
± 7.5%
14400
72
50
55
60
68
80
144
100
110
120
135
160
288
200
220
240
270
320
333
231
254
277
312
370
416
289
318
347
390
462
432
300
330
360
405
480
500
347
382
416
468
555
576
400
440
480
540
640
667
463
509
556
625
668
720
500
550
600
668
668
833
578
636
668
668
668
19920
100
50.2
55
60
68
80
200
100.4
110
120
135
160
333
167
184
200
225
267
400
200.8
220
240
270
320
500
250
275
300
338
400
667
335
369
402
452
536
833
418
460
502
564
668
1000
502
552
602
668
668
34500
172.5
50
55
60
68
80
345
100
110
120
135
160
517
150
165
180
203
240
690
200
220
240
270
320
a
55/65 °C rise rating on Eaton voltage regulators gives an additional 12% increase in
capacity if the tap-changer’s maximum current rating has not been exceeded. For loading
in excess of the above values, please refer to your Eaton representative.
b
Regulators are capable of carrying current corresponding to rated kVA when operated at
7200 V.
38
VR-32 and EVER-Tap™ Voltage Regulator
InstallatIon, operatIon, and MaIntenance InstructIons