Manual ESR5-NO-31-UC
07/2017 MN049014 EN www.eaton.com
31
16.4 Emergency stop monitoring / manual, monitored start / without cross-circuit detection
13
23
33
41
A2
S3 4
1 4
2 4
3 4
4 2
( )
ESR5-...
K1
K1
K2
S2
M
(N )
24-230V AC /DC
K2
K1
K2
M
S3 5
( )
L
A1
S
S
11
13
(+)
( )
S2 2
( )
S
S
2 1
10
(GND)
( )
S1 2
( )
S1
•
Two-channel emergency stop monitoring
•
Manual, monitored start
•
Monitoring of external, force-guided contactors
•
No cross-circuit detection in the sensor circuit
•
Suitable up to category 4, PL e (EN ISO 13849-1), SIL 3 (EN 62061), if
cross-circuits in the control to the actuator and the sensor circuit can be
ruled out
Figure 17:
Emergency stop monitoring / manual, monitored start / without cross-circuit
detection
Key:
Cross-circuits in the cable installation can be excluded if the
safety relay and external contactors K1 and K2 are located in the
same electrical installation space.
For sensor circuits in the field, prevent cross-circuits by using a
cable installation that is protected mechanically.
S1
Emergency stop button
S2
Manual reset device
K1/K2
Force-guided contactors