13 Startup
•
Apply the rated control circuit supply voltage
(24 V AC/DC ... 230 V AC/DC) at terminal blocks A1/A2.
The Power LED lights up.
•
Close the sensor circuit at S10/S11/S12/S13 and
S21/S22 as per the wiring.
The IN1/2 LED lights up.
Automatic start
The enabling current paths 13/14, 23/24 and 33/34 close.
The K1 and K2 LEDs light up.
Signaling current path 41/42 opens.
Manual, monitored start
▶
Press the reset button.
▶
Release the reset button.
The enabling current paths 13/14, 23/24 and 33/34 close.
The K1 and K2 LEDs light up.
Signaling current path 41/42 opens.