Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1
www.eaton.com/ePDU
63
info command
Use this command to display the device data defined by its name information (
info [name]
).
pdu#0>info ?
info [System]
info [Network]
info [User]
info [Access]
info [Time]
info [eMail]
info [SNMP]
info [NetworkManagement]
info [EnergyWise]
info [DaisyChain]
info [UserDefinedGroup]
info [PowerSchedule]
info [Summary]
info [Input1]
info [Input2]
NOTE 1
info [Gang]
info [Outlet]
info [Environment]
pdu#0>
NOTE 1
: On Dual Input ePDU only.
Usage
pdu#0>info <object>
where:
<object> = name of a simple object, an object of type array or a family of objects.
Example 1
pdu#0>info System.*
Name
Data Default RW/RO
----------------------------------------------------------------------
System.Contact String:31 "" RW
System.Location String:31 "" RW
System.Network.HostName String:31 "epduF0" RW
PDU.PowerSummary.iName String:31 "ePDU" RW
System.Ethernet.iVersion String:10 RO
System.FirmwareUpgradeMode Boolean 0 RW
System.FirmwareUpgrade Boolean 1 RW
System.Restart Boolean 0 RW
System.FactoryReset Boolean 0 RW
System.LogReset Boolean 0 RW
System.KeepIP Boolean 0 RW