Network Communication Configuration
Eaton ePDU G3 Operation Manual P-164000277—Rev 1
www.eaton.com/ePDU
41
255.255.yyy.yyy
6.
Set the network Gateway to the value required by your system administrator.
PDU#0>set System.Network.IPGateway zzz.zzz.zzz.zzz
zzz.zzz.zzz.zzz
7.
Wait 10 seconds. Use the reset button to restart the eNMC module and apply the new settings.
NOTE
You can also connect up to four ePDUs together using the Daisy Chain port and an
RJ-45 splitter (provided). This enables multiple ePDUs to communicate over one
Ethernet port.
NOTE
If you choose not to use the procedure to configure the communications module
without the DHCP server installed, you can connect to the ePDU using the default
address:
http://192.168.123.123
Verify Web Operation After Configuration
To verify the communications module is operational and that you can access the Web interface:
1.
Open a Web browser.
2.
Enter the IPv4 or IPv6 address in the address bar in the following format:
http://
<IPv4 address>
or
http://
<IPv6 address>
3.
When the user authentication pop-up dialog displays, type
admin
in the User name field and
admin
in the
Password field.
4.
The home page opens with the ePDUOverview page.