EMR-5000
IM02602012E
Electrical Discharge Immunity Test (ESD)
IEC 60255-22-2
IEC 61000-4-2
class 3
Air discharge
Contact discharge
8 kV
6 kV
Radiated Radio Frequency Electromagnetic Field Immunity Test
IEC 60255-22-3
IEC 61000-4-3
26 MHz – 80 MHz
80 MHz – 1 GHz
1 GHz – 3 GHz
10 V/m
35 V/m
10 V/m
Immunity to Conducted Disturbances Induced by Radio Frequency Fields
IEC 61000-4-6
class 3
150kHz - 80MHz
10 V
Power Frequency Magnetic Field Immunity Test
IEC 61000-4-8
class 4
continuous
3 sec
30 A/m
300 A/m
EMC Emission Tests
Radio Interference Suppression Test
IEC/CISPR22
IEC60255-26
DIN EN 55022
150kHz - 30MHz
Limit value class B
Radio Interference Radiation Test
IEC/CISPR22
IEC60255-25
DIN EN 55022
30MHz - 1GHz
Limit value class B
www.eaton.com
940