EMR-5000
IM02602012E
EMC Immunity Tests
Fast Transient Disturbance Immunity Test (Burst)
IEC 60255-22-4
IEC 61000-4-4
ANSI C37.90.1
class 4
Power supply, mains inputs
Other in- and outputs
±
4 kV, 2.5 kHz
±
2 kV, 5 kHz (coupling network)
±4
kV, 2.5 kHz (coupling clamp)
Surge Immunity Test (Surge)
IEC 60255-22-5
IEC 61000-4-5
class 4
Within one circuit
Circuit to ground
2 kV
4 kV
class 3
Communication cables to ground
2 kV
www.eaton.com
939