EMR-5000
IM02602012E
Manual Acknowledgment
•
Press the »Ack/Rst« button on the panel.
•
Select the item to be acknowledged via the softkeys:
•
Relay Outputs;
•
LEDs;
•
SCADA;
•
A trip command; or
•
All the above mentioned items at once.
•
Press the Softkey with the »Wrench-Symbol«.
•
Enter the password.
Manual Acknowledgment Via PowerPort-E
•
If PowerPort-E is not running, please start the application.
•
If device data have not been downloaded recently, select »Receive Data From The Device« from the »Device«
menu.
•
Double click on the »Operation« icon in the navigation tree.
•
Double click on the »Acknowledgment« icon within the operation menu.
•
Double click the entry within the pop-up that is to be acknowledged.
•
Press the »Execute immediately« button.
•
Enter the password.