System Alarms
Available Elements:
SysA
Within the System Alarms menu [SysA] the User can configure:
General Settings (activate/inactivate the Demand Management, optional assign a signal, that will block the Demand
Management);
Power Protection (please refer to section 32, 32V, 32VA);
Demand Management (Power and Current); and
THD Protection.
Please note, that all thresholds are to be set as primary values.
Demand Management
Demand is the average of system current or power over a time interval (window)
. D
emand management supports the
User to keep energy demand below target values bound by contract (with the energy supplier). If the contractual target
values are exceeded, extra charges are to be paid to the energy supplier.
Therefore, demand management helps the User detect and avoid averaged peak loads that are taken into account for
the billing. In order to reduce the demand charge respective to demand rate, peak loads, if possible, should be
diversified. That means, if possible, avoiding large loads at the same time. In order to assist the User in analyzing the
demand, demand management might inform the User by an alarm. The User might also use demand alarms and
assign them on relays in order to perform load shedding (where applicable).
Demand management comprises:
Watt Demand (Active Power);
VAr Demand (Reactive Power);
VA Demand (Apparent Power); and
Current Demand.