EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 26 of 107
Parameter
Description
Where to find:
Battery n SoC
Individual Battery SoC. Number of battery SoC
displayed is equal to number of battery LVD’s
configured.
Menu>System
Status>Battery
Battery n Charge
kWh
Individual Battery Charge kWh since last reset.
Number of battery charge energy meters is equal to
number of battery LVDs configured.
Battery n Discharge
kWh
Individual Battery Discharge kWh since last reset.
Number of battery discharge energy meters is equal
to number of battery LVDs configured.
Battery n Available
Ah
Individual Battery AH available. Number of battery
AH counters is equal to number of battery LVDs
configured.
Parameters will be displayed only for the configured number of batteries.
Configuration
Set the following parameters
Parameter
Description
Where to find:
No of Batt Fuses
Set the number of Battery fuse as per Battery bank
installed.
Display:
Menu>System Config>DC
Config>Batt Config
Web:
Menu>System Config>DC
Config>Batt Config
No of Batt LVD
Set minimum one LVD or it can be set as per
configuration selection. Number of current sensing
or installed shunt and number of LVD installed are
always same.
BATTERY TEMPERATURE COMPENSATION
As the ambient temperature of a battery drops (or rises) the voltage required to maintain full charge increases
(or decreases). Temperature Compensation automatically varies the charge voltage to cancel the effects of
changing temperature.
Enable Temperature Compensation for optimum battery life and battery capacity over a wider temperature
range.
Temperature Compensation does NOT function during a Battery Test.
Temperature compensation function should work when all below conditions are true:
•
BCL condition is completed.
•
Temperature Compensation function should be enabled, Menu>Settings>Battery Settings>Temp
Comp. Setting.
•
Battery charging current is < (BCL Factor% - 1%) of Battery Ah or Battery in float mode.