4.4 User settings
The following table displays the options that can be changed by the user.
Submenu
Available settings
Default settings
Local
settings
Language
[English] [Français] [Deutsch] [Español] [
Русский
]
[Português] [Italiano] [Simplified Chinese] [Japanese]
Menus, status, notices and alarms, UPS fault, Event Log
data and settings are in all supported languages.
English
Automatic message for user
configuration when UPS is
powered for the first time.
Date / time
Format: [International] [US]
[US]
LCD
Modify LCD screen brightness and contrast to be adapted
to room light conditions.
[0]
Audible
alarm
[Enabled] [Disabled on battery] [Always disabled]
Enable or disable the buzzer if an alarm occurs.
[Enabled]
Level: [0-8]
[6]
Protected
access
[Enabled] [Disabled]
Allow the user to lock the settings modification. Password
is: 0577
[Disabled]
In/Out
settings
Output
voltage
[200 V] [208 V] [220 V] [230 V] [240 V]
[208 V]
Input
thresholds
[Normal] [Extended]
Extended mode authorises lower input voltage (150V) w
ith
out transferring to battery.
This can be used if the load can withstand low voltage
supply.
[Normal]
Sensitivity
[High] [Low]
Low sensitivity extend the range of input frequency
accepted before transferring to battery.
[High]
Load
segments
[Auto start delay]
UPS:[No delay]; Group1:[3s];
Group2:[6s]
[Auto shutdown delay]
UPS:[Disabled]; Group1:
[Disabled]; Group2:[Disabled]
Overload
prealarm
[10%] … [105%]
Load % when overload alarm occurs
[105%]
ON/OFF
settings
Start/Restart
[Cold start]
[Auto restart]
[Auto start]
[Cold start] : ON
[Auto restart] : ON
[Auto start] : OFF