User-assembled network connection cables
The following components are available for assembling
different cable lengths:
• Supply cable
– Type - EASY-NT-CAB, cable 100 m, 4 x 0.18 mm
2
.
• Bus connection plug
– RJ45 plug, type: EASY-NT-RJ45 (8-pole)
• Tools
– Crimping tool for RJ45 plug, Type: EASY-RJ45-TOOL.
AWG 24, 0.2 mm
2
is the largest crimpable cross section.
Cable layout
4-core, twisted pair;
Figure 22:
Connection assignment
• ECAN_H data cable, pin 1, cable pair A.
• ECAN_L data cable, pin 2, cable pair A.
• Ground cable GND, pin 3, cable pair B.
• Select cable SEL_IN, pin 4, cable pair B.
h
The table on page 66 provides information for the
required cable cross-section of longer cable lengths,
taking the cable resistance into account.
A
1 ECAN_H
A
2 ECAN_L
B
3 GND (Ground)
B
4 SEL_OUT/SEL_IN
h
The most basic easyNet configuration operates with the
cables ECAN_H, ECAN_L, GND. The SEL_IN cable is only
used for automatic addressing and configuration.