Working with contacts and
relays
151
02/16 MN05013001Z EN
Function
If the jump coil is triggered, the rungs after the jump coil are
no longer processed. The states of the coils before the jump
will be retained, unless they are overwritten in rungs that
were not missed by the jump. Jumps are always made
forwards, i.e. the jump ends on the first contact with the
same number as that of the coil.
• Coil = jump on 1 state
• Contact only at the first leftmost contact = Jump label
The jump contact location is
always 1.
Power flow display
Jumped sections are indicated by the coils in the power flow
display.
All coils after the jump coil are shown with the symbol of the
jump coil.
h
Backward jumps cannot be executed due to the way in
which easySafety works. If the jump label does not come
after the jump coil, the jump will be made to the end of the
circuit diagram. The last rung is also skipped.
The same jump coil and contact can be used several times
as long as they are used in pairs, i.e.:
Coil
Ä
:1/skipped area/contact:1,
Coil
Ä
:1/skipped area/contact:1
etc.
h
Caution!
If rungs are skipped, the states of the coils are retained.
The time of started timing relays continues to run.