Installation
10/10 MN05003003Z-EN
28
Connecting expansion devices/network modules
Local expansion
X
Connect the devices to the expansion or to the network module
via the EASY-LINK-DS connection plug.
Remote expansion
Remote expansion units can be installed and run up to 30 m away
from the basic unit.
Figure 33: Connecting expansion devices with EC4-200
j
The following electrical separation is implemented
between the basic unit and an expansion unit (separation
always in local connection of expansion unit).
• Basic isolation 400 V AC (+10 %)
• Safe isolation 240 V AC (+10 %)
Units may be destroyed if the value 400 V AC +10 % is
exceeded, and may cause the malfunction of the entire
system or machine!
EASY-LINK-DS
EC4-200
EASY6…-RE/TE
EASY202-RE
EASY204-DP
EASY221-CO
EASY222-DN
EASY205-ASI
h
Basic unit and expansion unit can be provided with
different DC power supplies.
j
Warning!
The two-wire or multiple-wire cable between the devices
must comply with the insulation voltage requirement
which is stipulated for the installation environment.
Otherwise, a fault (ground fault, short-circuit) may lead to
the destruction of the units or injury to persons.
A cable such as NYM-0 with a rated operational voltage
of U
e
= 300/500 V AC is normally sufficient.
h
Terminals E+ and E– of the EASY200-EASY are protected
against short-circuits and polarity reversal. Functionality
is only ensured if E+ is connected with E+ and E- with E-.
Figure 34: Connecting remote expansion units to the EC4-200
E+ E–
E+ E–
EC4P-221/222-M…1
EASY6…-RE/-TE
EASY200-
EASY
EASY-LINK-DS
Summary of Contents for easyControl EC4-200
Page 4: ...II...
Page 10: ...10 10 MN05003003Z EN 6...
Page 14: ...10 10 MN05003003Z EN 10...
Page 22: ...10 10 MN05003003Z EN 18...
Page 38: ...10 10 MN05003003Z EN 34...
Page 62: ...10 10 MN05003003Z EN 58...
Page 78: ...10 10 MN05003003Z EN 74...
Page 96: ...10 10 MN05003003Z EN 92...