3 Commissioning
3.10 Commissioning an Net network
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
95
Figure 82:CONFIGURE menu
Requirement for the configuration using NET station 1:
•
You must have wired your network as a “passing through” cable routing.
•
All stations must be correctly connected to the NET and the termination
resistors must have been connected.
•
All stations have power, show the basic menu in the device display (the
status display) and are in operating mode STOP. The POW and NET LEDs
must be permanently lit.
Procedure
▶
Proceed to the CONFIGURE menu item and press the OK pushbutton.
You will be asked to acknowledge whether you want to configure the
system.
▶
Press OK.
CAUTION
The REMOTE IO, SEND IO and REMOTE RUN parameters
required for operation are not transferred to the connected
device with the NET configuration.
If you require a parameter setting that is different to the factory
setting, you can do this locally via the NET PARAMETERS menu
of the NET station concerned. An easier way is to carry out the
parameter setting in easySoft-Pro in conjunction with a program
transfer to the device concerned.
PROTECTION...
SYSTEM...
MENU LANGUAGE
CONFIGURATOR...
NET...
LINK...
Display NET only in STOP
operating mode.
NET PARAMETER...
STATIONS...
CONFIGURE
CONFIGURE?
CONFIGURATION
IN
PROGRESS.
Fault scenario
with ID conflict.
Fault scenario with
network fault.
ERR: ID CONFLICT
CONFIGURATION
OVERWRITE ?
ERR: TIME OUT
NET
-
PARAMETER...
STATIONS...
CONFIGURE
CONFIGURE?