3 Commissioning
3.11 Putting the SmartWire-DT into operation
98
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
3.11 Putting the SmartWire-DT into operation
For a better understanding read chapter „SmartWire-DT“, Page 282, before
commissioning SmartWire-DT.
Before switching on, check whether the power supply for the easy800-SWD
is connected correctly. The installation of the SWD line must also have been
carried out correctly with all stations connected.
You must have completed the following steps before commissioning:
1. POW supply voltage is connected
(
2. If necessary, connect the AUX supply voltage if contactors are used
(
3. SmartWire-DT connected to easy800-SWD
(
section “Install SmartWire-DT”, page 67).
4. All configured SWD stations are connected to the SWD line.
5. The bus termination must be connected.
Commissioning
▶
Switch on the POW supply voltage on the device.
The status of the LEDs on the device is as follows:
•
POW-LED:green continuous light
•
SWD-LED:red flashing
•
Config. LED: off
•
The SWD status LEDs on the SWD stations also flash green.
▶
Press the Config configuration button on easy800-SWD for at least 2 s.
The status of the LEDs on the device is as follows:
•
POW-LED:green continuous light
•
SWD-LED: orange flashing (during addressing);
then continuously lit green (after addressing)
•
Config. LED: green
DANGER
Unforeseen motor startup or unexpected connection of voltages
may cause death. When switching on the device, ensure that
the device switches to a controlled and safe operational state.