6 Internal
6.2 Delay times for inputs and outputs
190
Operating instructions
05/10 MN05013003Z-EN
www.eaton.com
Figure 93:
Switching behavior with input debounce disabled
Typical delay times with the debounce delay switched off are:
•
On delay for I1 to I12
•
0.25 ms (DC),
•
0.3 ms (easy-DA)
•
Off delay for
•
I1 to I6 and I9 to I12: 0.4 ms (easy-DC), 0.3 ms (easy-DA)
•
I7 and I8: 0.2 ms (DC), 0.35 ms (easy-DA)
6.2.2 Delay time with
-AB,
-AC basic units
The input delay with AC voltage signals depends on the frequency. The
appropriate values for 60 Hz are given in brackets:
•
Switch-on delay
•
80 ms at 50 Hz,
•
66 ms at 60 Hz
•
Off delay for
•
I1 to I6 and I9 to I12: 80 ms (66 ms)
•
I7 and I8: 160 ms (150 ms) with easy-AB
•
I7 and I8: 80 ms (66 ms) with easy-AC
Figure 94:
On delay for easy-AC, easy-AB
→
Ensure clean input signals when the debounce is deactivated as
easy reacts even to very short signals.
1
0
1
0
S1
B
B
B
B
B
B
A
C
I1
A
1
1
B
S1
t
SC2
Summary of Contents for easy500, easy700
Page 4: ...II...
Page 28: ...1 1 5 operating principles 24 Operating instructions 05 10 MN05013003Z EN www eaton com...
Page 210: ...7 What Happens If 7 3 Event 206 Operating instructions 05 10 MN05013003Z EN www eaton com...