Control commands for easy600
90
09/10 MN05013007Z-EN
Time switch
Ö
1 –
Ö
4: read actual value
(channel, ON time, OFF time)
Telegram structure
Byte
Meaning
Value (hex), sent by
Bit
M
S
Master
Slave
7 6 5 4 3 2 1 0
Attribute ID: Read
Ö
1 channel A
4B
–
0 1 0 0 1 0 1 1
Ö
1 channel B
4C
–
0 1 0 0 1 1 0 0
Ö
1 channel C
4D
–
0 1 0 0 1 1 0 1
Ö
1 channel D
4E
–
0 1 0 0 1 1 1 0
Ö
2 channel A
4F
–
0 1 0 0 1 1 1 1
Ö
2 channel B
50
–
0 1 0 1 0 0 0 0
Ö
2 channel C
51
–
0 1 0 1 0 0 0 1
Ö
2 channel D
52
–
0 1 0 1 0 0 1 0
Ö
3 channel A
53
–
0 1 0 1 0 0 1 1
Ö
3 channel B
54
–
0 1 0 1 0 1 0 0
Ö
3 channel C
55
–
0 1 0 1 0 1 0 1
Ö
3 channel D
56
–
0 1 0 1 0 1 1 0
Ö
4 channel A
57
–
0 1 0 1 0 1 1 1
Ö
4 channel B
58
–
0 1 0 1 1 0 0 0
Ö
4 channel C
59
–
0 1 0 1 1 0 0 1
Ö
4 channel D
5 A
–
0 1 0 1 1 0 1 0
0
Response
Read successful
–
C2
1 1 0 0 0 0 1 0
Command rejected
–
C0
1 1 0 0 0 0 0 0
0
1
Control byte switching timer
00
1
2
Control byte channel
00
2
3
Minute (switch point ON)
00
3
4
Hour (switch point ON)
00
4
5
Minute (switch point OFF)
00
5
6
Hour (switch point OFF)
00
M = master
S