7
System function introduction
E02A INTEGRATED RACK TYPE AIR CONDITIONER
UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com
4. System function introduction
The operation of the air conditioner is automatically controlled according to the temperature inside the cabinet. The
controller detects the return air temperature by temperature sensor and compares it with the set point to judge,
and then controls the compressor or fan.
4.1 Cooling
Cooling stop point=cooling set point cooling Delta T. When the rack internal temperature exceeds the cooling set
point (CoolingSP), the cooling will start; when the cabinet internal temperature is lower than the cooling stop
point, the cooling stops.
Parameter
Default value
Setting range
CoolSP
29˚C
[20~50]
Cool T
3˚C
[1~10]
INHT
65˚C
[20~80]
Setting point descriptione:
CoolSP: Set point when cooling starts.
Cool T: Temperature control sensitivity.
INHT: Internal high Temp. alarm point.
CAUTION!
For the reliable operation of the unit and the maximum energy efficiency, it is recommended that the user
should not randomly change the temperature set point.
4.2 Heating (Option)
Heating stop point=heating point+heating sensitivity. When the temperature inside the cabinet is lower than the
heating start-up point, the heating will start; when the temperature inside the cabinet is higher than the heating
stop point, the heating will stop.
Parameters
Default value
Setting range
HeatSP
0˚C
[-5~15]
Heat T
10˚C
[1~15]
Setting point descriptione:
HeatSP: Point when heating starts.
Cool T: Temperature control sensitivity.
CAUTION!
For the reliable operation of the unit and the maximum energy efficiency, it is recommended that the users
should not randomly change the temperature set point.