![Eaton DX-NET-PROFINET2-2 Manual Download Page 33](http://html1.mh-extra.com/html/eaton/dx-net-profinet2-2/dx-net-profinet2-2_manual_3803019033.webp)
4 Commissioning
4.3 Parameter settings
30
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
4.3.1 Configuration of the control signal terminals
The following control signal terminal configuration tables use the abbrevia-
tions and acronyms listed below:
Table 3:
Abbreviations and acronyms for control signal terminals
Abbreviation
Meaning
AI1 REF
Analog input AI1
Used as a speed setpoint input
AI2 REF
Analog input AI2
Used as a speed setpoint input.
AI2 Torque REF
Analog input AI2
Used as a torque setpoint input.
DIR
Used to select an operating direction
Used together with the START command.
• Low = Forward (FWD )
• High = Reverse (REV)
Note:
If there is a wire breakage and the REV operating direction is selected, this will cause
the drive to reverse!
Alternative: Use configuration with FWD/REV.
DOWN
Used to reduce the speed if a digital setpoint value is selected.
Used together with the UP command.
ENA
Variable frequency drive enable signal (ENA = Enable)
A start signal (START, FWD, REV) is additionally required for starting.
If ENA is removed, the drive will coast.
EXTFLT
External fault
FWD
Used to start the drive in the forward direction (FWD = Forward)
INV
Change of rotation (INV = Inverse)
The operating direction will be reversed as per the configured ramps.
• High = invert
• Low = Do not reverse
Pulse FWD (NO)
Pulse REV (NO)
Pulse STOP (NC)
Pulse control
REV
Used to start the drive in the reverse direction (REV = Reverse)
Select Quick-Dec
Quick stop
Select AI1 REF/AI2 REF
Used to select between the analog setpoint values on AI1 and AI2
• AI1 = Low
• AI2 = High
Select AI1 REF/f-Fix
Used to select between analog speed reference values at analog input 1
Select AI1 REF/f-Fix1
Used to select between analog speed reference values at analog input 1
Select BUS REF/AI2 REF
Used to select between setpoint values
Select BUS REF/f-Fix
Used to select between setpoint values
Select BUS REF/f-Fix1
Used to select between setpoint values
Select DIG REF/AI2 REF
Used to select between the digital speed reference value (set with the keypad or with
the UP and DOWN commands) and analog setpoint value AI2 REF