1 Series
1.4 Pin assignment
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
9
1.4 Pin assignment
1.4.1 PROFINET connection
Figure 3:
Connecting the RJ45 plug
The connection to the PROFINET field bus is established via an RJ45 plug in
the lower area of the DX-NET-PROFINET2-2 communication interface.
Generally, connection cables with RJ45 plugs for PROFINET are available as
standard ready-for-use cables. They can also be prepared individually.
This will require the connections shown below (pin assignment).
Figure 4:
Pin assignment for RJ45 plugs (PROFINET connection)
PIN
Meaning
1
TD+
2
TD-
3
RD+
4
To GND via RC circuit
5
To GND via RC circuit
6
RD-
7
To GND via RC circuit
8
To GND via RC circuit
RJ45
1
2
3
4
5
6
7
8